Manufacturer: Yokogawa Electric Corporation
	Yokogawa Screw Y9306LB 
	 
	Hardware Specifications 
	Yokogawa Screw Y9306LB 
	For the installation specifications and the environmental conditions common to the systems, refer to “Vnet/IP System Overview (Vnet/IP Edition)” (GS 33K01A10- 50E). 
	  
	Processor 
	VR5432 (133 MHz) 
	  
	Main Memory Capacity 
	32 Mbyte 
	  
	Memory Protection During Power Failure 
	Battery 
	Battery Back-up for Main Memory: Max. 72 hours 
	Battery Recharge Time: Min. 48 hours 
	  
	FCU Status Contact Output 
	2 terminals (NC, C) 
	Contact Points open during FCU failure 
	Contact Rating: 30 V DC, max. 0.3 A 
	  
	Communication Interface 
	Vnet/IP Interface: Dual-redundant 
	  
	For more details, refer to “Integrated Production Control System CENTUM VP System Overview (Vnet/IP Edition)” (GS 33K01A10-50E). 
	  
	No. of Node Units Connectable 
	Max. 14/FCU 
	The total number of ESB Bus Node Units and ER Bus Node Units that can be connected to FCU are 14 or less. (ESB Bus Node Units: 9 or less) 
	LFS1500 allows up to 3 nodes, and can be expanded to 14 if LFS1550 Application capacity Expansion Package (for AFV10 ) is added. 
	To connect a node unit to the FCU, a Node Unit Expansion License (Option code: /NDEL) is required for the node unit. 
	  
	Module configuration 
	Power Supply Module (PW481 or PW482 or PW484): 
	Two modules in case of a dual-redundant configuration. 
	Processor Module (CP451): Two modules in case of a dual-redundant configuration. 
	I/O Modules(*1): Max. 8 
	*1: Non-standard components. 
	  
	ESB Bus Node Units Connection 
	Yokogawa Screw Y9306LB
 
	When connecting an ESB Bus Node Unit to FCU, install ESB Bus Coupler Module (EC401) on FCU. EC401 must be installed in slot 7 and slot 8. For the dual-redundant configuration of the processor modules, EC401 must be installed in both slot 7 and slot 8. 
	In case ESB Bus has a single configuration, EC401 must be installed in slot 7 and keep slot 8 empty. 
	  
	ER Bus Node Units Connection 
	When connecting an ER Bus Node Unit to FCU, install ER Bus Interface Master Module (EB401) on FCU. 
	To make single configuration, EB401 must be installed in an odd-number slot, and keep empty the right side of the installed EB401. 
	See “ER Bus Interface Master Module (for FIO)” (GS 33K50F40-50E) for further information. 
	  
	Power Supply 
	Voltage: 100-120 V AC, Frequency: 50/60 Hz 
	Voltage: 220-240 V AC, Frequency: 50/60 Hz 
	Voltage: 24 V DC 
	Specify with Suffix Codes. 
	  
	Power Consumption 
	100-120 V AC: 200 VA 
	220-240 V AC: 230 VA 
	24 V DC: 5.5 A 
	  
	Weight 
	Approx. 7 kg (AFV10S) 
	Approx. 8 kg (AFV10D) 
	  
	Mounting 
	19-inch Rack Mounting: 
	Rack mount (8 x M5 screws) 
	Insulation bush (accessory) 
	  
	Connection 
	Power Supply: M4 screw terminal connection Grounding: M4 screw terminal connection Contact Output: M4 screw terminal connection Network: Connect UTP cable (CAT5e or better) to Layer 2 switch. 
	  
	Regulatory Compliance 
	Yokogawa Screw Y9306LB
 
	For the detailed information of following standards, see “System Overview (Vnet/IP Edition)” (GS 33K01A10-50E). 
	Safety Standards 
	[CSA] (for 100-120 V AC power supply) 
	[CE Marking] (for 220-240 V AC power supply) 
	EMC Conformity Standards 
	[CE Marking] (for 220-240 V AC and 24 V DC power supply) 
	[C-Tick Marking] (for 220-240 V AC and 24 V DC power supply) 
	[KC Marking] (for 220-240 V AC and 24 V DC power supply) 
	Standards for Hazardous Location Equipment 
	[FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) 
	[Type n] (for 24 V DC power supply) 
	Models and Suffix Codes 
	Duplexed Field Control Unit 
	Yokogawa Screw Y9306LB
 
	 
	
		
			
				| 
					 
						  
					 
				 | 
				
					 
						  
					 
				 | 
				
					 
						Description 
					 
				 | 
			
			
				| 
					 
						Model 
					 
				 | 
				
					 
						AFV10D 
					 
				 | 
				
					 
						Duplexed Field Control Unit (for Vnet/IP and FIO, for 19-inch Rack Mountable) 
					 
				 | 
			
			
				| 
					 
						  
					 
					
						  
					 
					
						  
					 
					
						  
					 
					
						  
					 
					
						Suf?x 
					 
					
						Codes 
					 
				 | 
				
					 
						-S 
					 
				 | 
				
					 
						Standard type 
					 
				 | 
			
			
				| 
					 
						4 
					 
				 | 
				
					 
						Dual-Redundant Vnet/IP, Dual-Redundant power supply 
					 
				 | 
			
			
				| 
					 
						1 
					 
				 | 
				
					 
						Always 1 
					 
				 | 
			
			
				| 
					 
						1 
					 
				 | 
				
					 
						100–120 V AC power supply 
					 
				 | 
			
			
				| 
					 
						2 
					 
				 | 
				
					 
						220–240 V AC power supply 
					 
				 | 
			
			
				| 
					 
						4 
					 
				 | 
				
					 
						24 V DC power supply 
					 
				 | 
			
			
				| 
					 
						5 
					 
				 | 
				
					 
						Basic type with no explosion protection 
					 
				 | 
			
			
				| 
					 
						6 
					 
				 | 
				
					 
						With ISA Standard G3 option and no explosion protection 
					 
				 | 
			
			
				| 
					 
						E 
					 
				 | 
				
					 
						Basic type with explosion protection 
					 
				 | 
			
			
				| 
					 
						F 
					 
				 | 
				
					 
						With ISA Standard G3 option and explosion protection 
					 
				 | 
			
			
				| 
					 
						1 
					 
				 | 
				
					 
						LFS1500 Control Function for Field Control Station (for Vnet/IP and FIO) 
					 
				 | 
			
			
				| 
					 
						Option 
					 
					
						Code 
					 
				 | 
				
					 
						  
					 
					
						/ATDOC 
					 
				 | 
				
					 
						  
					 
					
						Explosion Protection Manual (*1) 
					 
				 | 
			
		
	
 
	*1:      Select the option code "/ATDOC" to follow the ATEX Directive
for use in potentially explosive atmospheres. 
	Insulating Partition
Kit 
	
		
			
				| 
					 
						  
					 
				 | 
				
					 
						  
					 
				 | 
				
					 
						Description 
					 
				 | 
			
			
				| 
					 
						Part No. 
					 
				 | 
				
					 
						T9083ND 
					 
				 | 
				
					 
						Insulating Partition Kit 
					 
				 | 
			
		
	
	Con?guration of Insulating Partition
Kit 
	
		
			| 
				 
					  
				 
			 | 
			
				 
					  
				 
			 | 
			
				 
					Description 
				 
			 | 
		
		
			| 
				 
					  
				 
				
					Part No. 
				 
			 | 
			
				 
					T9083NE 
				 
			 | 
			
				 
					Insulating Partition 
				 
			 | 
		
		
			| 
				 
					T9083NG 
				 
			 | 
			
				 
					Insulating Partition for V net 
				 
			 | 
		
		
			| 
				 
					Y9306LB 
				 
			 | 
			
				 
					2 screws for T9083NG 
				 
			 |