Manufacturer: Yokogawa Electric Corporation
STARDOM: FCN, FCN-500, FCN-100, FCN-RTU, FCJ
Yokogawa Digital Output Module NFDV551-P60
Standard Specifications
Digital Output Modules
The Digital Output Modules output 32-channel or 64-channel transistor contact signals.
Yokogawa Digital Output Module NFDV551-P60
|
Item
|
Specifications
|
|
Model
|
NFDV551
|
NFDV557
|
NFDV561
|
|
Number of output channels
|
32
|
32
|
64
|
|
Rated applied voltage
|
24 V DC
|
24 V DC
|
24 V DC
|
|
Load voltage (*1)
|
24 V DC, 50 mA
|
24 V DC, 50 mA
|
24 V DC, 100 mA
|
|
Field power supply voltage
range
|
20.4 to 26.4 V
|
20.4 to 26.4 V
|
20.4 to 26.4 V
|
|
Output ON voltage maximum
value
|
2 V DC
|
2 V DC
|
2 V DC
|
|
Leak current maximum value
when output OFF
|
0.1 mA
|
0.1 mA
|
0.1 mA
|
|
Output format
|
Current sink
|
Current sink
|
Current sink
|
|
Maximum load current (*2)
|
100 mA/channel, 26.4 V
|
100 mA/channel, 26.4 V
|
100 mA/channel, 26.4 V
|
|
Withstanding voltage
|
Between output signal and system: 2 kV AC (*5)
Between commons: 500 V AC, common minus (–) side every 16-channel
|
|
Functions
Status output
|
ON/OFF status output function
|
ON/OFF status output function
|
ON/OFF status output function
|
|
Output fallback (*3) (*4)
|
HOLD: Holds the current states when the fallback action is triggered.
OFF: Resets all the output channels to off when the fallback action is triggered.
NO: Performs no fallback action.
|
|
Output response time
|
3 ms or less (for status output)
|
|
Maximum current consumption
|
700 mA (5 V DC)
60 mA (24 V DC, field power
supply)
|
550 mA (5 V DC)
60 mA (24 V DC, field power
supply)
|
780 mA (5 V DC)
120 mA (24 V DC, field power
supply)
|
|
Weight
|
0.2 kg
|
0.3 kg
|
0.3 kg
|
|
External connection
|
Pressure clamp terminal, MIL
connector cable (*5)
|
Pressure clamp terminal
|
MIL connector cable (*5)
|
*1: An external field power supply (24 V DC) is required for each module.
*2: Connect a spark killer diode when driving DC relay. Yokogawa Digital Output Module NFDV551-P60
*3: The fallback detection time is 4 seconds.
*4: HOLD, OFF, or NO should be chosen for all channels commonly. Yokogawa Digital Output Module NFDV551-P60
*5: The withstanding voltage for using MIL connector cable depends on the electrical specifications of its cable.
Models and Suffix Codes
Digital Output Module
Yokogawa Digital Output Module NFDV551-P60
|
|
|
Description
|
|
Model
|
NFDV551
|
Digital Output Module (32-channel, 24 V DC, Isolated)
|
|
Suffix Codes
|
-P
|
Standard type
|
|
6
|
With status display and no explosion protection
|
|
F
|
With status display and explosion protection
|
|
0
|
Basic type
|
|
1
|
With ISA Standard G3 option
|
|
Option Codes
|
/D5S00
|
With Pressure Clamp Terminal Block for Digital Output [Model : NFTD5S-00]
|
|
/D5S10
|
With Pressure Clamp Terminal Block for Digital Output (surge absorber) [Model : NFTD5S-10]
|
|
/CCC01
|
With Connector Cover for MIL Cable [Model : NFCCC01]
|