- 如果您對該產(chǎn)品感興趣的話,可以
- 產(chǎn)品名稱:mV Input Multiplexer Module AMM22M Yokogawa
- 產(chǎn)品型號:AMM22M
- 產(chǎn)品展商:Yokogawa
- 產(chǎn)品文檔:無相關(guān)文檔
簡單介紹
Yokogawa Electric Corporation, mV Input Multiplexer Module AMM22M Yokogawa, mV Input Multiplexer Module AMM22M Yokogawa, for CENTUM CS 3000 and CENTUM CS 1000 systems. Please contact us: tekrachel @ 163.com
產(chǎn)品描述
mV Input Multiplexer Module AMM22M Yokogawa
The specifications of I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
mV Input Multiplexer Module AMM22M Yokogawa
l Multiplexer Module mV Input Multiplexer Module AMM22M Yokogawa
These modules receive up to 16 points from DC voltage, mV, thermocouple and RTS. Measuring inputs can be specified per point.
|
Item
|
Specifications
|
|
Model
|
AMM12T AMM12C
|
AMM22M AMM22C
|
AMM22T AMM22TJ (*2)
|
AMM32T AMM32TJ (*3) AMM32C AMM32CJ (*3)
|
AMM25C (*2)
|
|
Input
|
16
|
16
|
16
|
16
|
15
|
|
Input signal
|
DC voltage
|
mV
|
Thermocouple IEC Standard Type K, T, J, E, B, R,
IEC Standard
Type N
|
RTD
JIS JPt100 or JIS Pt100 (DIN Pt 100)
3-wire type
|
Termocouple IEC Standard Type K, T, J, E, B, R, S
IEC Standard Type N, mV. Channel 16 is used for RJC port.
|
|
Input range
|
-10 to 10 V DC
|
-100 to 100 mV DC
|
-100 to 100 mV DC
|
-200 to 600°C
|
-100 to 100 mV
|
|
Allowable input voltage
|
-30 to 30 V DC
|
-0.5 to 4.0 V DC
|
-0.5 to 4.0 V DC
|
-
|
-0.5 to 4.0 V DC
|
|
Input resistance
|
1 M?
|
-
|
1 M?
|
|
Signal isolation
|
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
|
|
Data update period
|
1 s
|
|
Accuracy
|
±4 mV
|
±40 μV
|
±40 μV
|
±0.15 ?
|
±40 μV
|
|
Burnout detection
|
-
|
Select from UP/DOWN/OFF.
|
|
Input parallel connection
|
Permitted (burnout OFF)
|
Not permitted
|
Permitted (burnout OFF)
|
|
How installed
|
Installed in the I/O module nest.
|
|
How connected
|
Connected to the terminal of the I/O module with M4 screws. Use a KS1, KS2 or KS3 cable for AMM12C, a
KS1 cable for AMM22C/AMM25C, and a KS8 cable for AMM32C.
|
|
Effect of ambient tem- perature change
|
For 10 °C change :
DC voltage: ±8 mV or less mV input: ±80 μV or less
Thermocouple input: ±80 μV or less RTD Input: ±0.3 ? or less
|
For 10 °C change :
±80 μV or less
|
|
Current consumption
|
500 mA or less (5.0 V DC)
|
|
How input signals are specified
|
Specify input signals and range by software setting.
|
*1: If measured temperature is lower than 0 °C, multiply
the above value by the following coef?cient (K): mV Input Multiplexer Module AMM22M Yokogawa
*2: AMM22TJ and AMM25C conform to IEC584-1995.
*3: AMM32TJ and AMM32CJ
conform to IEC751-1995.