Yokogawa Small Electric Power Input Module AAM21 (mV, Thermocouple, and RTD Input Module)
GENERAL
I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
STANDARD SPECIFICATIONS
I/O Module Nest
Yokogawa Small Electric Power Input Module AAM21
Power Supply:
5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/
PFCD Field Control Station
Installation: Node Interface Unit, I/O Expansion Rack,
or Model PFCS/PFCD Field Control Station.
External
Dimensions: 125mm (W) x 130mm (D) x 248mm (H);
AMN51: 137.5mm (W) x 225mm (D) x 254 (H);
AMN52: 233.3mm (W) x 225mm (D) x 254mm (H)
Weight: Max. 2.5 kg
(AMN52. This weight does not include
I/O Modules.)
|
Installation Restrictions for I/O Module Nest
Yokogawa Small Electric Power Input Module AAM21
|
Model AMN12 High-speed Nest for Analog I/O Modules (*1)
-Always install in Nest No. 1.
-Do not install any I/O module nests in Nests No. 2 through No. 4.
-When using non-AMN12 I/O Module Nest with AMN12, always install it in Nest No. 5
Model AMM22T, AMM22TJ (*2)
-Do not install non-AMM22T, AMM22TJ I/O module
below AMM22T, AMM22TJ because AMM22T, AMM22TJ is a module for thermocouple entry. If there were a heat source below AMM22T, AMM22TJ, a reference junction compensation
error occur.
-If there is another module (heat source) below AMM22T, AMM22TJ when using 19” Rack Mountable Type,
a thermal shield must be inserted between AMM22T, AMM22TJ
and the heat source (See Figures 6 and 7).
Model AMN51 Nest for Communication Cards (*3)
-Only
one nest is installable in PFCS/PFCD.
Its position is fixed as Nest No. 2.
AMN52 Nest for PROFIBUS Communication Module
-Only one nest is installable in PFC£. Its position is fixed as Nests No. 1 and 2. AMN52 cannot be combined with AMN51.
Small Electric Power Input Module
This
module receives signals from mV,
thermocouple, RTD and potentiometer.
Yokogawa Small Electric Power Input Module AAM21
|
Item
|
Specifications
|
|
Model
|
AAM21, AAM21J (*4)
|
|
Input signal
|
mV
|
JIS,IEC Standard Thermocouple type K, T, J, E, B (*1), R, S, IEC Standard type N
|
RTD JIS JPt100 or
JIS Pt100 (DIN Pt100)
3-wire type
|
3-wire potentiometer’s
|
|
Input range
|
-50 to 150 mV
|
-50 to 150 mV
|
0 to 333 ?
|
The total residence is within 100 to 2000 ?, and the span is 50 % or more of the total resistance.
(*2)
|
|
Allowable input voltage
|
-0.5 to 4.0 V DC (between terminals B-C)
|
-
|
|
Input resistance
|
1 M V at power-up (3 k V at power-down)
|
-
|
|
Accuracy
|
±20 μV
|
±20 μV
|
±0.08 V
|
±0.2 %
|
|
Data update period
|
100 ms
|
|
Signal source resistance
|
1000 ? or less
|
150 ? or less (wiring resistance per wire)
|
|
RJC input
|
-
|
-10 to 70 °C
|
-
|
|
RJC accuracy
|
-
|
Within ± 1 °C (*3)
|
-
|
|
Measuring current
|
-
|
1 mA
|
-
|
|
Auxiliary voltage output
|
1 to 5 V DC (Signal ground is shared with system) Output resistance: 1 ? or less
Allowable load resistance: 10 k? or more
Output range: 0.5 to 5.5 V DC Accuracy: ±12 mV
|
|
Burnout detection
|
Select from UP/DOWN/OFF (*5)
|
|
Burnout detection time
|
Within 60 sec
|
|
Burnout detection current
|
0.1 μA (terminal B only) (*5)
|
|
How installed
|
Installed in AMN11 Nest for Analog I/O Modules
|
|
How connected
|
Connected to the terminals of the I/O module nest with M4 screws
|
|
Signal isolation
|
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
|
|
Current consumption
|
150 mA or less (5.0 V DC)
|
|
Input linearization
|
None
|
Available
|
Available
|
None
|
|
Effect of signal source resistance/wiring resistance (burnout is OFF)
|
1 k? of signal source resistance: Input conversion
± 20 μV or less
|
Wiring resistance 10 ? for terminals A and C: In- put conversion ±40 m? or less (Wiring of terminals
A and C must have the same resistance)
|
-
|
|
Effect of ambient temperature change
|
For 10 °C change: mV input: ±40 μV
Thermocouple input: ±40 μV
RTD input: ±0.16 ?
Potentiometer input: ±0.4 % of span
Auxiliary voltage output: ±24 mV
|
-
|
|
How input signals are specified
|
Specify input signals and range by software setting.
|
Option Specifications for Thermocouple
When
using the AAM21 for thermocouple
input, order the temperature compensation module for each channel.
|
|
|
Description
|
|
Model
|
AAM21, AAM21J
|
|
|
Option Code
|
/RJ
|
Temperature Compensation Module for Thermocouple Input
|