Yokogawa CENTUM CS 3000 and CENTUM CS 1000 system
Yokogawa Current/Voltage Input Module AAM10
GENERAL
I/O Modules and I/O Module Nests (for RIO) for CENTUM CS 3000 and CENTUM CS 1000 systems.
STANDARD SPECIFICATIONS for Yokogawa Current/Voltage Input Module AAM10
I/O Module Nest
Yokogawa Current/Voltage Input Module AAM10
Power Supply:
5.0 V DC supplied from Model AND50, ANS50, AND20, ANS20 Node Interface Unit or Model PFCS/
PFCD Field Control Station
Installation: Node Interface Unit, I/O Expansion Rack,
or Model PFCS/PFCD Field Control Station.
External
Dimensions: 125mm (W) x 130mm (D) x 248mm (H);
AMN51: 137.5mm (W) x 225mm (D) x 254 (H);
AMN52: 233.3mm (W) x 225mm (D) x 254mm (H)
Weight: Max. 2.5 kg
(AMN52. This weight does not include
I/O Modules.)
Current/Voltage Input Module (Simplified Type) for Yokogawa Current/Voltage Input Module AAM10
This
module receives 4-20 mA from 2-wire
transmitters and 1-5 V standardized signals.
|
Items
|
Specifications
|
|
Model
|
AAM10
|
|
Input signal
|
1 to 5 V DC
|
4 to 20 mA DC (*1) (*2) (It is possible to supply power to a transmitter)
|
|
Input resistance
|
1 M? at power-up (100 k? at power-down)
|
250 ?
|
|
Allowable input voltage/current
|
-10 to 30 V DC
|
40 mA DC or less
|
|
Transmitter power supply
|
-
|
25.0 to 25.5 V DC (Output current limit: 60 mA DC or less )
|
|
Auxiliary voltage output
|
None
|
|
Square root extraction
|
None
|
|
Accuracy
|
Voltage input: ±4 mV; Current input: ±16 mA
|
|
Effect of ambient temperature change
|
For 10 °C change: Voltage input: ±8 mV Current input: ±32 μA
|
|
Data update period
|
50 ms
|
|
Current consumption
|
250 mA or less (5.0 V DC)
|
|
Signal isolation
|
Input signals are isolated between systems. Withstanding voltage: 1500 V AC/min
|
|
How installed
|
Installed in the I/O Module Nest.
|
|
How connected
|
Connected to the terminals of the I/O Module Nest with M4 screws.
|
|
How input signals are specified
|
Specify input signals and range by software setting.
|