Yokogawa ProSafe-RS Analog Input Module SDV144-S33
STANDARD SPECIFICATIONS
Yokogawa ProSafe-RS Analog Input Module SDV144-S33
Input Module
Yokogawa ProSafe-RS Analog Input Module SDV144-S33 accept contact signals from the ?eld. SDV144-S33 can be made
dual-redundant.
|
Item
|
Speci?cations
|
|
Model
|
SDV144
|
|
Number of inputs
|
16-channel, module isolation
|
|
Input signal
|
No-voltage contact ON: 1 k? maximum OFF: 100 k? minimum
|
|
Input current
|
6 mA ± 20 %
(External power supply, 24 V DC at 0 ? input)
|
|
Contact rating
|
24 V DC +20 % / -10 % (*1), 10 mA or greater
|
|
External power supply
|
24 V DC +20 % / -10 % (*1) Current capacity: 200 mA
|
|
Instantaneous maximum permissible input voltage
|
30.0 V DC
|
|
Input response time
|
40 ms maximum
|
|
Withstand voltage
|
2 kV AC between input signal and system, 16-input line collectively connected (*2)
|
|
Current consumption
|
290 mA maximum (5 V DC)
140 mA maximum (24 V DC)
|
|
Weight
|
0.36 kg (For pressure clamp terminal block or MIL cable)
0.41 kg (With signal cable interface adapter)
|
|
External connection
|
Pressure clamp terminal
MIL cable
Dedicated signal cable (AKB331)
|
*1: The contact rating and the external power supply of SDV144-S33 style code S1, S2 and S3 are 24 V DC ± 5 %.
*2: When connecting SDV144-S33 and SED4D terminal board using the dedicated signal cable, the withstand voltage is 500 V AC (between input signal lines and system). If MIL connector cables are used, the withstand voltage depends on their cable’s electrical speci?cations.
MODEL AND SUFFIX CODES
Yokogawa ProSafe-RS Analog Input Module SDV144-S33
Digital Input Module
|
|
|
Description
|
|
Model
|
SDV144
|
Digital Input Module (16-channel, module isolation)
|
|
Suf?x Codes
|
-S
|
Standard type
|
|
5
|
For pressure clamp terminal block or MIL cable with no explosion protection
|
|
6
|
With signal cable interface adapter and no explosion protection (*1)
|
|
E
|
For pressure clamp terminal block or MIL cable with explosion protection
|
|
F
|
With signal cable interface adapter and explosion protection (*1)
|
|
3
|
With ISA Standard G3 and temperature (-20 to 70 °C)
|
|
Option Codes
|
/B4S00
|
With pressure clamp terminal block for digital input (without surge absorber) [Model: STB4S-00]
|
|
/B4S10
|
With pressure clamp terminal block for digital input (with surge absorber) [Model: STB4S-10]
|
|
/B4D00
|
Dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*2) [Model: STB4D-00]
|
|
/B4D10
|
Dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*2) [Model: STB4D-10]
|
|
/PRP
|
With prevention pin of false insertion (*3)
|
|
/CCC01
|
With connector cover for MIL cable (for ?at ribbon cable) [Model: SCCC01]
|
|
/CCC02
|
With connector cover for MIL cable (for discrete wire) [Model: SCCC02]
|
*1: When SDV144-S33-S63 or -SF3 is selected, you cannot choose the option code for a pressure
clamp terminal block and MIL
cable connector.
*2: When this module is used in dual-redundant con?guration, order an additional module with the same speci?cation but
without option codes. Yokogawa ProSafe-RS Analog Input Module SDV144-S33
*3: When SDV144-S33-S63
or -SF3 is selected, you can choose the option code for prevention pin of false insertion.