Manufacturer: Yokogawa Electric Corporation
	
	
		Yokogawa Analog Input Module AAI141-H50/A4S00 
	
	Yokogawa DCS 
	CENTUM VP  
	STANDARD SPECIFICATIONS 
	Current/Voltage Input Modules (Non-Isolated) 
	Yokogawa Analog Input Module AAI141-H50/A4S00
 
	These modules mainly receive 4 to 20
mA DC or 1 to 5 V DC standardized signal from 2-wire/4-wire transmitters. 
	They can be used in dual redundant
configuration. 
	
		
			
				| 
						Items 
					 | 
						Specifications 
					 | 
			
				| 
						Model 
					 | 
						AAI141 (*1) 
					 | 
						AAV141 
					 | 
						AAV142 
					 | 
			
				| 
						Number
  of input channels 
					 | 
						16,
  non-isolated  
					 | 
						16,
  non-isolated(differential input)  
					 | 
						16,
  non-isolated 
					 | 
			
				| 
						Input
  signal 
					 | 
						4
  to 20 mA DC 
					 | 
						1
  to 5 V DC(allowable common mode voltage ± 1 V or less) 
					 | 
						-10
  to 10 V DC 
					 | 
			
				| 
						Allowable
  input current/voltage 
					 | 
						27
  mA 
					 | 
						 ±7.5 V  
					 | 
						±13
  V 
					 | 
			
				| 
						Withstanding
  voltage 
					 | 
						 —  
					 | 
						—  
					 | 
						— 
					 | 
			
				| 
						Input
  resistance 
					 | 
						Power
  ON 
					 | 
						400
  Ω (at 20 mA) to 1000 Ω(at 4 mA) (*2)  
					 | 
						1
  MΩ or more  
					 | 
						1
  MΩ or more 
					 | 
			
				| 
						Power
  OFF 
					 | 
						 500 kΩ or more  
					 | 
						340
  kΩ or more  
					 | 
						660
  kΩ or more 
					 | 
			
				| 
						Accuracy 
					 | 
						 ±16 μA  
					 | 
						±4
  mV 
					 | 
						 ±20 mV 
					 | 
			
				| 
						Data
  update period 
					 | 
						10
  ms 
					 | 
			
				| 
						Step
  response time 
					 | 
						100
  ms 
					 | 
			
				| 
						Transmitter
  power supply 
					 | 
						14.8
  V or more (at 20 mA) (*3)26.4 V or less (at 0 mA)(output current limit: 27
  mA) 
					 | 
						— 
					 | 
						 — 
					 | 
			
				| 
						Setting
  of 2-wire or 4-wire transmitter 
					 | 
						 For each channel by setting pin 
					 | 
						 —  
					 | 
						— 
					 | 
			
				| 
						Drift
  due to ambient temperature change 
					 | 
						±16
  μA/10 °C 
					 | 
						 ±4 mV/10 °C 
					 | 
						 ±20 mV/10 °C 
					 | 
			
				| 
						Maximum
  current consumption 
					 | 
						310
  mA (5 V DC),450 mA (24 V DC) 
					 | 
						 350 mA (5 V DC)  
					 | 
						350
  mA (5 V DC) 
					 | 
			
				| 
						Weight 
					 | 
						0.2
  kg  
					 | 
						0.2
  kg  
					 | 
						0.2
  kg 
					 | 
			
				| 
						External
  connection 
					 | 
						 Pressure clamp terminal, KS cable, MIL
  connector cable 
					 | 
			
				| 
						HART
  communication (*4) 
					 | 
						Available 
					 | 
						 — 
					 | 
						 — 
					 | 
		
	
 
	*1: This Yokogawa Analog Input Module AAI141 does not allow a
Zener barrier to be connected. If the module Yokogawa Analog Input Module AAI141-H50/A4S00 is to be used in intrinsically
safe applications, use an isolation barrier. 
	*2: Viewed from the terminals,
module input resistance is, depending on the current flowing: 
	250 Ω +(voltage drop (3 V maximum) in the input
protection circuit)/(current value) 
	*3: This Yokogawa Analog Input Module AAI141-H50/A4S00 voltage is developed
between connecting terminals for this module’s
2-wire transmitter. When calculating if transmitter minimum operating voltage
requirement will be satisfied, remember to allow for voltage drop in external
wiring. 
	*4: R3.02 or later version supports
HART function. When installing the module with HART function to a remote node,
the firmware of EB401 must be Rev 2 or later. 
For HART function specifications, refer to “HART Communication
Package (for A□I□□□-H) (GS 33Q03L70-31E).”
	MODELS AND SUFFIX CODES 
	Yokogawa Analog Input Module AAI141-H50/A4S00 
	
		
			| 
					  
				 | 
					  
				 | 
					 Description
				 | 
		
			| 
					 Model
				 | 
					 AAI141
				 | 
					 Analog
  Input Module (4 to 20 mA, 16-channel, Non-Isolated)
				 | 
		
			| 
					 Suffix Codes
				 | 
					 -S
				 | 
					 Standard
  type
				 | 
		
			| 
					 -H
				 | 
					 With
  digital communication (HART protocol)
				 | 
		
			| 
					 5
				 | 
					 With
  no explosion protection
				 | 
		
			| 
					 E
				 | 
					 With
  explosion protection
				 | 
		
			| 
					 0
				 | 
					 Basic
  type
				 | 
		
			| 
					 3
				 | 
					 With
  ISA Standard G3 option and temperature (-20 to 70 °C) option
				 | 
		
			| 
					 Option Codes
				 | 
					 /K4A00
				 | 
					 With
  KS Cable Interface Adapter [Model: ATK4A-00]
				 | 
		
			| 
					 /A4S00
				 | 
					 With
  Pressure Clamp Terminal Block for Analog [Model: ATA4S-00]
				 | 
		
			| 
					 /A4S10
				 | 
					 With
  Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10]
				 | 
		
			| 
					 /A4D00
				 | 
					 With
  Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00]
				 | 
		
			| 
					 /A4D10
				 | 
					 With
  Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10]
				 | 
		
			| 
					 /CCC01
				 | 
					 With
  Connector Cover for MIL Cable [Model: ACCC01]
				 |