Manufacturer: Yokogawa Electric Corporation
Yokogawa Analog Input Module AAI143-H50/A4D00
Yokogawa DCS
CENTUM VP
STANDARD SPECIFICATIONS
Current/Voltage Input Modules (Non-Isolated)
Yokogawa Analog Input Module AAI143-H50/A4D00
These modules mainly receive 4 to 20
mA DC or 1 to 5 V DC standardized signal from 2-wire/4-wire transmitters.
They can be used in dual redundant
configuration.
*1: This Yokogawa Analog Input Module AAI141 does not allow a
Zener barrier to be connected. If the module Yokogawa Analog Input Module AAI143-H50/A4D00 is to be used in intrinsically
safe applications, use an isolation barrier.
*2: Viewed from the terminals,
module input resistance is, depending on the current flowing:
250 Ω +(voltage drop (3 V maximum) in the input
protection circuit)/(current value)
*3: This Yokogawa Analog Input Module AAI143-H50/A4D00 voltage is developed
between connecting terminals for this module’s
2-wire transmitter. When calculating if transmitter minimum operating voltage
requirement will be satisfied, remember to allow for voltage drop in external
wiring.
*4: R3.02 or later version supports
HART function. When installing the module with HART function to a remote node,
the firmware of EB401 must be Rev 2 or later.
For HART function specifications, refer to “HART Communication
Package (for A□I□□□-H) (GS 33Q03L70-31E).”
MODELS AND SUFFIX CODES
Yokogawa Analog Input Module AAI143-H50/A4D00
|
|
|
Description
|
|
Model
|
AAI141
|
Analog
Input Module (4 to 20 mA, 16-channel, Non-Isolated)
|
|
Suffix Codes
|
-S
|
Standard
type
|
|
-H
|
With
digital communication (HART protocol)
|
|
5
|
With
no explosion protection
|
|
E
|
With
explosion protection
|
|
0
|
Basic
type
|
|
3
|
With
ISA Standard G3 option and temperature (-20 to 70 °C) option
|
|
Option Codes
|
/K4A00
|
With
KS Cable Interface Adapter [Model: ATK4A-00]
|
|
/A4S00
|
With
Pressure Clamp Terminal Block for Analog [Model: ATA4S-00]
|
|
/A4S10
|
With
Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10]
|
|
/A4D00
|
With
Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00]
|
|
/A4D10
|
With
Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10]
|
|
/CCC01
|
With
Connector Cover for MIL Cable [Model: ACCC01]
|